Menu

 Technical Specifications

 Technical Specifications

Product model SRR4014 SRR4034
Rated voltage of fieldbus input power 5VDC (4.5V ~ 5.5V)
Rated current of fieldbus input power ≤30mA
Input voltage range on the field side 24 VDC (20.4 V ~ 28.8 V)
Output points 4 4
Output types Voltage type Current type
Output signals Disable,-10V to+-10V~+10V to 10V, -5V~+5V, 0V~5V and 1V~5V (adjustable range, -10V~+10V by default) Disable, 4mA~20mA and 0mA~20mA (adjustable range, 0mA~20mA by default)
Channel response time 200us/ch200us/4ch
Resolution 16bits
Accuracy 0.1% at 25℃; 0.3% within the whole temperature range
Load impedance (voltage type) ≥ 2kΩ (1kΩ accuracy: 3 % at 25℃; 5 ‰ with the whole temperature range) -
Load impedance (current type) - ≤500Ω
No affect on the system When the ±15V power supply is damaged and short-circuited, the system +5V power supply shall not be affected
Output protection Overload protection, open circuit protection and short circuit protection (with automatic recovery mechanisms)
Potential isolation There is no isolation between channels, and there is isolation between channel and backplane fieldbus, and between channel and power voltage
Isolation withstand voltage 500VDC
Rated current loss 30mA
Power consumption 0.15W
Optional clearing/holding functions in non-OP state Support
Channel indicator Green LED